Installation Tips
Here are the most common new installation errors to avoid:
Panels equipped with the redundant off option
- Redundant off float not connected.
- Pump will not run in hand or automatic mode on a TD type panel.
- Pump will not run in automatic mode on a standard panel. It will however, run in hand mode.
- If the float is not available, secure jumper wire in place of the redundant off float.
Panels equipped with thermal cutout connection
- Pump does not run in Hand or Automatic mode.
- Verify thermal cutout is connected.
- To test panel operation:
Disconnect voltage. Tag and remove the thermal cutout wires. Use a jumper wire (on panel terminal block) in place of the thermal cutout wires.
Reconnect voltage. If pump runs in hand mode, thermal cutout connection is incorrect or possible defective thermal switch in pump.
Here are some installation tips to assist you in your new installation:
Incoming power:
Correct incoming voltage: Example---208v or 240v or 480V
Control\Alarm voltage: L1-----L1------N
Alarm-Control-Neutral
For code some places require two 120V lines to come in and share neutral, otherwise bring in the hot lead to a L1 (TB1:1) and neutral to N (TB1:3) and jumper L1 (TB1:1) and L1 (TB1:2) together.
Floats: Have to be in correct order and on correct terminal block position
4-Float, Duplex
|
3-Float Duplex
|
Simplex
|
Alarm(TB1:9&10)
|
Lag\Alarm(TB1:7&8) |
Alarm(TB1:8&9) |
Lag(TB1:7&8)
|
Lead(TB1:5&6) |
Start(TB1:6&7) |
Lead(TB1:5&6) |
Stop(TB1:3&4) |
Stop(TB1:3&4) |
Stop(TB1:3&4) |
Jumper on (TB1:8&9) |
Time Dose, Simplex |
Time Dose, Duplex |
Alarm(TB1:1&2) |
Alarm(TB1:7&8) |
Timer Override-wide |
Timer Override-wide |
Angle (optional) (TB1:3&4) |
Angle (optional) (TB1:5&6) |
Low Level Cutout-wide angle(TB1:5&6) |
Low Level Cutout-wide angle(TB1:3&4) |
Redundant Off (optional) (TB1:7&8) |
Redundant Off (optional) (TB1:1&2) |
Make sure:
Breakers ON
Overload ON
Motor protective switch ON
Power switch (PCB) ON
HOA (hand\off\auto) switch to correct position.
Automatic is all the way down toward pump run lights on PCB.
Lead lag switch to correct position. 3 position switch, center is alternate.
3 Phase panels:
Floating wire, has a white tag, hooked up to correct transformer position for appropriate voltage.
Seal Fail\Thermal Cutout:
Hooked up to correct terminal block connections.
Seal fail=infinite ohms open
Thermal cutout=0 ohms closed